8. To select the required sensitivity, set DIP switch 5 of
SW3 as follows:
ON = HIGH sensitivity
OFF= LOW sensitivity
Note: The recommended setting is HIGH. However,
in cases of extreme environmental problems or if
unexplained false alarms are experienced, it may be
necessary to set the sensitivity to LOW. Setting the
device to LOW sensitivity will require a greater amount
of movement in order to trigger the device.
9. Connect the PP3 Alkaline battery to the battery clip.
The LED indicator behind the lens will rapidly ash for
approximately 2-3 minutes until the PIR has stabilised
when the LED will stop ashing rapidly.
10. Check that the detector circuit board is located and
set in the correct position to give the detection zone
pattern required.
To adjust the PCB position simply slide it up or down
ensuring that the location legs are aligned with the
required position number marked on the board.
PCB Position Range
1 6m
3 9m
5 12m
11. Ret the PIR Detector rear cover by offering the
detector up to the rear cover and locate the clips in the
top edge into the rear cover. Push the lower edge of
the detector into place and ret the xing screw in the
bottom edge of the PIR to secure in position. Do not
over-tighten the screw as this may damage the casing.
TESTING THE PIR DETECTOR:
12. Ensure that the LED indicator has stopped ashing
rapidly.
13. Walk into and move slowly around the protected
area, each time the detector senses movement the
LED indicator behind the lens will ash.
14. If necessary remove the detector from the wall and
adjust the mounting position of the circuit board within
the detector. Repeat step 13 until the detection range
is correct for your needs. (In most cases no adjustment
will be required).
15. Recongure the PIR Detector for Normal Operation
with DIP switch 4 of SW3 OFF and ret in position on
the wall.
IMPORTANT: In normal operation, the LED
indicator behind the detector lens will not ash on
movement detection, (unless the battery is low).
Note: When the detector is fully installed i.e. battery
cover tted and in operating mode; in order to conserve
power and maximise battery life the PIR Detector will
only detect movement if there has been no movement
detected within the previous 2 minutes.
MAGNETIC CONTACT
DETECTORS
The Magnetic Contact Detector comprises 2 parts;
Detector and Magnet. They are designed to be tted to
either doors or windows with the Magnet mounted on
the opening part of the door/window and the Detector
mounted to the frame.
When the protected door or window is opened and the
Magnet is moved away from the Detector an alarm will
be triggered if the system is Armed, (unless the Siren is
in Service Mode).
The Magnetic Contact Detector has the facility to
connect an additional wired Magnetic Contact. This
must be of a normally closed contact type with the
contact being opened in order to generate an alarm
condition.
The Magnetic Contact Detector is powered by two
1 2 3 4 5
ON




















1 2 3 4 5
ON